UL 3289/3321/3173/3271/3344 XLPE CABLE
RR Kabel
Cable & Wires
Standard: UL – Std. 758. Complies to CSA No. 22.2 210 and 127
Nominal Voltage: 600V
Test Voltage (Spark Test):
AWG 22 and 20: 5kV
AWG 18 to 10: 6kV
≥ AWG 8: 7.5kV
Temperature Range: Flexible -5°C to +150°C. Fixed installation -50°C to +150°C
Temperature at Conductor: Max. UL : +150°C
Bending Radius: Approx. 5 x cable ø